EasyManua.ls Logo

Siemens SINAMICS S Series - F07330 Flying restart: Measured search current too low; F07331 FlyRestart: Not supported; A07350 (F) Drive: Measuring probe parameterized to a digital output; A07400 (N) Drive: DC link voltage maximum controller active

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of faults and alarms
Faults and Alarms
3-1535
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F07330 Flying restart: Measured search current too low
Drive object: VECTOR
Reaction: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: During a flying restart, it was identified that the search current reached is too low.
It is possible that the motor is not connected.
Remedy: Check the motor feeder cables.
F07331 FlyRestart: Not supported
Drive object: VECTOR
Reaction: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: It is not possible to power-up with the motor rotating (no flying restart). In the following cases, the "flying restart" func-
tion is not supported:
Permanent-magnet and separately-excited synchronous motors (PEM, FEM): Operation with V/f characteristic.
Permanent-magnet synchronous motor (PEM): Sensorless operation without a Voltage Sensing Module (VSM)
being connected.
Remedy: - de-activate the "flying restart" function (p1200 = 0).
- change the open-loop/closed-loop control mode (p1300).
- connect a Voltage Sensing Module (VSM) (voltage measurement).
A07350 (F) Drive: Measuring probe parameterized to a digital output
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The measuring probe is connected to a bi-directional digital input/output and the terminal is set as output.
Alarm value (r2124, decimal):
9: DI/DO 9 (X122.8)
10: DI/DO 10 (X122.10)
11: DI/DO 11 (X122.11)
13: DI/DO 13 (X132.8)
14: DI/DO 14 (X132.10)
15: DI/DO 15 (X132.11)
Remedy: - set the terminal as input (p0728).
- de-select the measuring probe (p0488, p0489, p0580).
Reaction upon F: OFF1
Acknowl. upon F: IMMEDIATELY
A07400 (N) Drive: DC link voltage maximum controller active
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The DC link voltage controller has been activated because the upper switch-in threshold has been exceeded (r1242).
The ramp-down times are automatically increased in order to maintain the DC link voltage (r0026) within the permis-
sible limits. There is a system deviation between the setpoint and actual speeds.
When the DC link voltage controller is switched-out (disabled), this is the reason that the ramp-function generator
output is set to the speed actual value.
See also: p1240 (Vdc controller or Vdc monitoring configuration)
Remedy: If the controller is not to intervene:
- increase the ramp-down times.
- disable the Vdc max controller
If the ramp-down times are not to be changed:
- use a chopper or regenerative feedback unit
Reaction upon N: NONE
Acknowl. upon N: NONE

Table of Contents

Related product manuals