List of parameters
Parameters
1-939
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets and displays the CANopen NMT state.
Values: 0: Initializing
4: Stopped
5: Operational
127: Pre-operational
128: Reset node
129: Reset Communication
Note: The value 0 (initialization) is only displayed and cannot be set.
Description: Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8740, p8741
Note: Corresponds to the CANopen object 1400 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8740, p8741
Note: Corresponds to the CANopen object 1401 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8685 CBC NMT states / NMT states
CU_S (CAN) Can be changed: C1(1), U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 129 127
p8700[0...1] CBC receive PDO 1 / Receive PDO 1
SERVO (CAN), VEC-
TOR (CAN)
Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 9204, 9206
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex
p8701[0...1] CBC receive PDO 2 / Receive PDO 2
SERVO (CAN), VEC-
TOR (CAN)
Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 9204, 9206
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex