Parameters
List of parameters
1-808
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the type of analog outputs of the Terminal Board 30 (TB30).
Values: 4: Voltage output (-10 V ... +10 V)
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description: Sets the type of analog outputs of terminal module 31 (TM31).
p4076[x] = 1, 4 correspond to a voltage output (p4074, p4078, p4080, p4083 are displayed in V).
p4076[x] = 0, 2, 3 correspond to a current output (p4074, p4078, p4080, p4083 are displayed in mA).
Values: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (4 mA ... +20 mA)
3: Current output (-20 mA ... +20 mA)
4: Voltage output (-10 V ... +10 V)
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: Refer to: p4077, p4078, p4079, p4080
Note: When changing p4076, the parameters of the normalization characteristic (p4077, p4078, p4079, p4080) are over-
written with the following default values:
For p4076 = 0, 3, p4077 is set to 0.0 %, p4078 to 0.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V.
For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
Description: Sets the normalization characteristic for the analog outputs of Terminal Board 30 (TB30).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note: The parameters for the characteristic do not limit.
r4076[0...1] TB30 analog outputs, type / TB30 AO type
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
4 4 -
p4076[0...1] TM31 analog outputs, type / TM31 AO type
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 4
p4077[0...1] TB30 analog outputs, characteristic value x1 / TB30 AO char x1
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]