Parameters
List of parameters
1-274
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the send and receive telegram.
Values: 3: Standard telegram 3, PZD-5/9
999: Free telegram configuration with BICO
Dependency: Refer to: F01505, F01506
Note: If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Values: 0: Free telegram configuring with p0915/p0916
Description: Sets the number of tolerated consecutive sign-of-life errors of the clock-cycle synchronous master.
The sign-of-life signal is normally received in PZD4 (control word 2) from the master.
Dependency: Refer to: p2045, r2065
Refer to: F01912
Note: The sign-of-life monitoring is disabled for p0925 = 65535.
Description: Displays the operating mode.
1: Closed-loop speed controlled operation with ramp-function generator
2: Closed-loop position controlled operation
3: Closed-loop speed controlled operation without ramp-function generator
p0922 PROFIdrive telegram selection / PD Telegr_sel
TM41 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
3 999 999
p0922 PROFIdrive telegram selection / PD Telegr_sel
TM15, TM17 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 2481, 2483
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 0 0
p0925 PROFIdrive clock synchronous sign-of-life tolerance / PD SoL_tol
CU_CX32, CU_S,
SERVO, TM41, VEC-
TOR (n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 1
r0930 PROFIdrive operating mode / PD operating mode
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -