List of parameters
Parameters
1-761
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p3863
Refer to: F30027
Warning: It must be carefully ensured that the binector outputs BO: p3864.n are correctly interconnected and also that the
appropriate digital outputs are correctly connected-up.
If the interconnection/connection is incorrect, in the case of an active DC link fast discharge, the software could exe-
cute another function (incorrect function) via binector outputs BO: p3864.n or could also permanently control the DC
link fast discharge even if the line contactor is closed.
Note: The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis" for-
mats.
Description: Sets the signal source for the signal "pre-alarm I*t shutdown (X21.3) of the Braking Module.
BI: p3865[0...7] = 0 signal --> no pre-alarm, I*t shutdown
BI: p3865[0...7] = 1 signal --> pre-alarm I*t shutdown (A06901)
Dependency: Refer to: A06901
Note: The pre-alarm I*t shutdown is only possible for "booksize" formats. This function is not supported for "chassis" for-
mats.
Description: Sets the signal source for the "fault" signal of the Braking Module (X21.4 for "booksize" formats and X21.3 for
"chassis" formats).
BI: p3866[0...7] = 0 signal --> fault (A06900)
BI: p3866[0...7] = 1 signal --> No fault
For a 1 signal, an acknowledgement via BO: r3861 is automatically carried out at certain time intervals.
Dependency: Refer to: A06900
Description: Sets the configuration when operating a long stator motor.
Dependency: Refer to: p3871, p3872, p3873, p3874, r3875, p3876, p3878, p3879
05 Fast discharge Braking Module 6 High Low -
06 Fast discharge Braking Module 7 High Low -
07 Fast discharge Braking Module 8 High Low -
p3865[0...7] BI: Braking Module pre-warning I*t shutdown / BM I*t shutdown
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9951
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p3866[0...7] BI: Braking Module fault / BM fault
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9951
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p3870 Long stator configuration / Long stator config
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate long stator help functions Active Inactive -
01 Suppress Gx_ZSW.14 Active Inactive -