A01488 Topology: Comparison EnDat encoder missing in the actual topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected an EnDat encoder in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: - re-configure the drive belonging to the encoder in the commissioning software project (encoder configuration) and
download the new configuration into the drive unit.
- delete the drive belonging to the encoder in the commissioning software project and download the new configura-
tion into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
A01489 Topology: Comparison motor with DRIVE-CLiQ missing in the actual topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a motor with DRIVE-CLiQ in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: - re-configure the drive belonging to this motor in the commissioning software project and download the new config-
uration into the drive unit.
- delete the drive belonging to this motor in the commissioning software project and download the new configuration
into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
F01505 (A) BICO: Interconnection cannot be established
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A PROFIdrive telegram has been set (p0922).
An interconnection contained in the telegram, was not able to be established.
Fault value (r0949, interpret decimal):
Parameter receiver that should be changed.
Remedy: Establish another interconnection.
Reaction upon A: NONE
Acknowl. upon A: NONE
F01506 (A) BICO: No standard telegram
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The standard telegram in p0922 is not maintained and therefore p0922 is set to 999.
Fault value (r0949, interpret decimal):
BICO parameter for which the write attempt was unsuccessful.