List of parameters
Parameters
1-327
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the configuration for the expanded ramp-function generator.
Caution: Re bit 00 = 1:
If the ramp-up time is longer than the ramp-down time (p1120 > p1121), then there is an acceleration step at the
zero crossover. This can have a negative impact on the mechanical system.
Note: Re bit 00 = 1:
When the direction change is changed there is no rounding-off before and after the zero crossover.
Description: Sets the signal source for "setpoint 2 enable".
Description: Sets the signal source for speed setpoint 1 of the speed controller.
Dependency: The effectiveness of this setpoint depends on, e.g. STW1.4 and STW1.6.
Refer to: r0898, p1140, p1142, p1160, r1170
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the velocity setpoint 1 of the speed controller.
Dependency: The effectiveness of this setpoint depends on, e.g. STW1.4 and STW1.6.
Refer to: r0898, p1140, p1142, p1160, r1170
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1151[0...n] Ramp-function generator configuration / RFG config
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Disable rounding-off at the zero cross-over Yes No 3070
p1152 BI: Setpoint 2 enable / Setp 2 enable
SERVO (Extended
brk), VECTOR
(Extended brk)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2711
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 899.15
p1155[0...n] CI: Speed controller speed setpoint 1 / n_ctrl n_set 1
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1550, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p1155[0...n] CI: Velocity controller, velocity setpoint 1 / v_ctrl n_set 1
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1550, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0