Parameters
List of parameters
1-350
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the DC braking time (duration).
Dependency: Refer to: p1230, p1231, p1232, p1234, r1239
Description: Sets the starting speed for DC braking.
If the actual speed falls below this threshold, then DC braking is activated.
Dependency: Refer to: p1230, p1231, p1232, p1233, r1239
Description: Sets the starting speed for DC braking.
If the actual velocity falls below this threshold, then DC braking is activated.
Dependency: Refer to: p1230, p1231, p1232, p1233, r1239
Description: Sets the signal source for the contactor feedback signal for external armature short-circuit.
Dependency: Refer to: p1230, p1231, p1236, p1237, r1239
Notice: In order that the pulses are not enabled when the contactor is closed, the contactor feedback signal must lag by a
sufficiently long time when opening the contactor.
Note: 1 signal: The contactor is closed.
0 signal: The contactor is open.
p1233[0...n] DC braking time / DCBRK time
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 7017
P-Group: Functions Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0.0 [s] 3600.0 [s] 1.0 [s]
p1234[0...n] Speed at the start of DC braking / DCBRK n_start
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 7017
P-Group: Functions Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 210000.00 [RPM]
p1234[0...n] DC braking, starting velocity / DCBRK v_start
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 7017
P-Group: Functions Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 1000.00 [m/min]
p1235[0...n] BI: External armature short-circuit, contactor feedback signal / ASC ext feedback
SERVO, VECTOR Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0