Parameters
List of parameters
1-340
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the monitoring time of the automatic restart (AR).
Dependency: Refer to: p1210, r1214
Caution: A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Notice: After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note: The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. After fault F07320 occurs, the power-on command must be withdrawn and all of the
faults acknowledged so that the automatic restart can be re-activated.
The monitoring is de-activated with p1213 = 0. If the time in p1213 is set lower than in p1212, then fault F07320 is
also generated at each restart.
The monitoring time must extended, if the faults that occur cannot be immediately and successfully acknowledged
(e.g. for faults that are permanently present).
Description: Sets the monitoring time of the automatic restart (AR).
Dependency: Refer to: p1210, r1214
Caution: A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Notice: After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note: The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully started again
(flying restart and magnetization of the motor must have been completed: r0056.4 = 1), then fault F07320 is output.
The monitoring is de-activated with p1213 = 0. If p1213 is set lower than the sum of p1212, the magnetizing time
p0346 and the additional delay time due to the flying restart, then fault F07320 is generated at each restart. If, for
p1210 = 1, the time in p1213 is set lower than in p1212, then fault F07320 is also generated at each restart.
The monitoring time must extended, if the faults that occur cannot be immediately and successfully acknowledged
(e.g. for faults that are permanently present).
Description: Automatic restart (AR) status word.
p1213 Automatic restart, monitoring time line supply return / AR t_mon line sup
A_INF, B_INF,
S_INF
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [s] 1999.0 [s] 0.0 [s]
p1213 Automatic restart, monitoring time line supply return / AR t_mon line sup
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [s] 1999.0 [s] 0.0 [s]
r1214.0...15 CO/BO: Automatic restart, status / AR status
A_INF, B_INF,
S_INF
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -