List of parameters
Parameters
1-323
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p1141, p1142
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 4 = 0: Inhibits the ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
Description: Sets the signal source for control word 1 bit 5 (enables ramp-function generator/ stops ramp-function generator)
Dependency: Refer to: p1140, p1142
Notice: The ramp-function generator is, independent of the status of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Note: Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen)
Bit 5 = 1: Enable ramp-function generator
Description: Sets the signal source for control word 1 bit 5 (enables ramp-function generator/ stops ramp-function generator)
Dependency: Refer to: p1140, p1142
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen)
Bit 5 = 1: Enable ramp-function generator
Description: Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
p1141[0...n] BI: Start ramp-function generator / Start RFG
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2442, 2443,
2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1141 BI: Start ramp-function generator / Start RFG
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1142[0...n] BI: Enable speed setpoint / Enable n_set
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2441, 2442,
2443, 2501, 2711
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1