Siemens SINAMICS S Series - p1141[0...n] BI: Start ramp-function generator; Start RFG; p1141 BI: Start ramp-function generator; Start RFG; p1142[0...n] BI: Enable speed setpoint; Enable n_set

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-323
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p1141, p1142
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 4 = 0: Inhibits the ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
Description: Sets the signal source for control word 1 bit 5 (enables ramp-function generator/ stops ramp-function generator)
Dependency: Refer to: p1140, p1142
Notice: The ramp-function generator is, independent of the status of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Note: Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen)
Bit 5 = 1: Enable ramp-function generator
Description: Sets the signal source for control word 1 bit 5 (enables ramp-function generator/ stops ramp-function generator)
Dependency: Refer to: p1140, p1142
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen)
Bit 5 = 1: Enable ramp-function generator
Description: Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
p1141[0...n] BI: Start ramp-function generator / Start RFG
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2442, 2443,
2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1141 BI: Start ramp-function generator / Start RFG
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1142[0...n] BI: Enable speed setpoint / Enable n_set
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2441, 2442,
2443, 2501, 2711
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1