F31115 (N, A) Encoder 1: Amplitude error track A or B (A^2 + B^2)
Drive object: All objects
Reaction: A_INFEED: NONE
SERVO: ENCODER (IASC / DCBRAKE, NONE)
VECTOR: ENCODER (IASC / DCBRAKE, NONE)
Acknowledge: PULSE INHIBIT
Cause: The amplitude (A^2 + B^2) does not lie within the tolerance bandwidth (software monitoring function).
SMC20:
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25 % / +20 %).
On the other hand, the response threshold is < 230 mV (frequency characteristic).
SMC10:
The nominal signal level is at 2900 mV (2.0 Vrms). The response threshold is < 1070 mV.
Fault value (r0949, interpret decimal):
Low word:
Signal level, track A (16 bits with sign).
High word:
Signal level, track B (16 bits with sign).
SMC20:
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
SMC10:
A signal level of 2900 mV peak value corresponds to the numerical value 6666 hex = 26214 dec.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy: - check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- with measuring systems without their own bearing system: Adjust the scanning head and check the bearing system
of the measuring wheel.
- for measuring systems with their own bearing system: Ensure that the encoder housing is not subject to any axial
force.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F31116 (N, A) Encoder 1: Amplitude error monitoring track A + B
Drive object: All objects
Reaction: A_INFEED: NONE
SERVO: ENCODER (IASC / DCBRAKE, NONE)
VECTOR: ENCODER (IASC / DCBRAKE, NONE)
Acknowledge: IMMEDIATELY
Cause: The amplitude of the rectified encoder signals A and B is not within the tolerance bandwidth (hardware monitoring).
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25 % / +20 %).
On the other hand, the hardware response thresholds are at < 176 mV and > 1.35 V.
Fault value (r0949, interpret decimal):
Low word: Signal level, track A (16 bits with sign).
High word: Signal level, track B (16 bits with sign).
A signal level of 500 mV corresponds to the numerical value 5333 hex = 21299 dec.
These analog values are not measured at the same time with the hardware fault output.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy: - check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE