Parameters
List of parameters
1-744
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
The INTERNAL voltage actual values are used for synchronization. The effects that a (sinusoidal) filter - that is con-
nected between the Motor Module and motor - has on the voltage actual values are taken into account (theoreti-
cally) by appropriately selecting p0230.
VSM: Voltage Sensing Module
Description: Sets the drive object number of the Voltage Sensing Module (VSM) used for the line-drive synchronization.
Dependency: Refer to: p3800, p3802
Note: VSM: Voltage Sensing Module
Description: Sets the signal source to switch-in/switch-out for the line-drive synchronization.
BI: p3802 = 1 signal:
The line-drive synchronization is switched-in.
Dependency: Refer to: p3800, p3801
Description: Displays the control word for the line-drive synchronization.
Note: Re bit 00:
For a 1 signal, p3800 > 0 is set.
Description: Displays the target frequency for the line-drive synchronization.
Dependency: Refer to: A07941
p3801[0...n] Sync-line-drive, drive object number / Sync DO_No
VECTOR Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 62 1
p3802[0...n] BI: Sync-line-drive enable / Sync enable
VECTOR Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
r3803.0 CO/BO: Sync-line-drive control word / Sync STW
VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Sync-line-drive selected Yes No -
r3804 CO: Sync-line-drive target frequency / Sync f_target
VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]