Description: Sets the number of Drive Data Sets (DDS).
Description: Using the parameter, each Drive Data Set (= index) is assigned the associated Motor Data Set (MDS).
The parameter value therefore corresponds to the number of the assigned motor data set.
Description: Using the parameter, each Drive Data Set (= index) is assigned the associated Encoder Data Set (EDS) for
encoder 1.
The parameter value therefore corresponds to the number of the assigned encoder data set.
Example:
Encoder data set 0 should be assigned to encoder 1 in drive data set 2.
--> p0187[2] = 0
Note: A value of 99 means that no encoder has been assigned to this drive data set (not configured).
Description: Using the parameter, each Drive Data Set (= index) is assigned the associated Encoder Data Set (EDS) for
encoder 2.
The parameter value therefore corresponds to the number of the assigned encoder data set.
Note: A value of 99 means that no encoder has been assigned to this drive data set (not configured).
p0180 Number of Drive Data Sets (DDS) / DDS count
SERVO, TM41, VEC-
TOR
Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: - Func. diagram: 8565
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 32 1
p0186[0...n] Motor Data Sets (MDS) number / MDS number
SERVO, VECTOR Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dynamic index: DDS, p0180 Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 15 0
p0187[0...n] Encoder 1 encoder data set number / Enc 1 EDS number
SERVO, VECTOR Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dynamic index: DDS, p0180 Func. diagram: 1580, 8570
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 99 99
p0188[0...n] Encoder 2 encoder data set number / Enc 2 EDS number
SERVO, VECTOR Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dynamic index: DDS, p0180 Func. diagram: 1580, 8570
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 99 99