Parameters
List of parameters
1-140
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Dependency: Refer to: r0334, r1937
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
This parameter is not used for induction motors (p0300 = 1xx).
Description: Sets the force constant of the synchronous motor.
p0316 = 0: The force constant is calculated from the motor data.
p0316 > 0: The selected value is used as force constant.
Dependency: Refer to: r0334, r1937
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
Description: Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Dependency: Refer to: r0334
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
This parameter is not used for induction motors (p0300 = 1xx).
p0316[0...n] Motor torque constant / Mot kT
SERVO Can be changed: C2(1, 3), U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 28_1 Unit selection: p0100
Not for motor type: ASM, REL, FEM Expert list: 1
Min Max Factory setting
0.00 [Nm/A] 100.00 [Nm/A] 0.00 [Nm/A]
p0316[0...n] Motor force constant / Mot kT
SERVO (Lin) Can be changed: C2(1, 3), U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 29_1 Unit selection: p0100
Not for motor type: ASM, REL, FEM Expert list: 1
Min Max Factory setting
0.00 [N/Arms] 1000.00 [N/Arms] 0.00 [N/Arms]
p0316[0...n] Motor torque constant / Mot kT
VECTOR Can be changed: C2(1, 3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 28_1 Unit selection: p0100
Not for motor type: ASM, REL, FEM Expert list: 1
Min Max Factory setting
0.00 [Nm/A] 100.00 [Nm/A] 0.00 [Nm/A]