Siemens SINAMICS S Series - F08510 (A) COMM BOARD: Send configuration data invalid; A08511 (F) COMM BOARD: Receive configuration data invalid

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of faults and alarms
3-1602
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: Check the parameterizing telegram (Ti, To, Tdp, etc.).
Reaction upon F: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F08510 (A) COMM BOARD: Send configuration data invalid
Drive object: A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction: A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: COMM BOARD did not accept the send-configuration data.
Fault value (r0949, interpret decimal):
Return value of the send-configuration data check.
Remedy: Check the send configuration data.
Reaction upon A: NONE
Acknowl. upon A: NONE
A08511 (F) COMM BOARD: Receive configuration data invalid
Drive object: A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The drive unit did not accept the receive-configuration data.
Alarm value (r2124, interpret decimal):
Return value of the receive-configuration data check.
0: Configuration accepted.
1: Connection established to more drive objects than configured in the device. The drive objects for process data
exchange and their sequence was defined using p0978.
2: Too many data words for input or output to a drive object. A max. of 16 words is permitted for SERVO and VEC-
TOR; a max. of 5 words for A_INF, TB30, TM31 and CU320.
3: Uneven number of bytes for input or output.
4: Setting data for synchronization not accepted.
5: Drive still not in cyclic operation.
6: Buffer system not accepted.
7: Cyclic channel length too short for this setting.
8: Cyclic channel address not initialized.
9: 3-buffer system not permitted.
10: DRIVE-CLiQ fault.
11: CU-Link fault.
12: CX32 not in cyclic operation.
Remedy: Check the receive configuration data.
Re alarm value = 1:
Check the list of the drive objects with process data exchange (p0978). With p0978[x] = 0, all of the following drive
objects in the list are excluded from the process data exchange.
Reaction upon F: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY