Description: Sets the torque threshold value for the signal "Torque setpoint < torque threshold value 1" (BO: r2198.10).
Dependency: Refer to: p2195, r2198
Description: Sets the force threshold value for the signal "Torque setpoint < torque threshold value 1" (BO: r2198.10).
Dependency: Refer to: p2195, r2198
Description: Sets the speed threshold for the message "Motor locked" (BO: r2198.6).
Dependency: Refer to: p0500, p2177, r2198
Description: Sets the velocity threshold for the message "Motor locked" (BO: r2198.6).
Dependency: Refer to: p0500, p2177, r2198
p2174[0...n] Torque threshold value 1 / M_thresh val 1
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 7_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 5.13 [Nm]
p2174[0...n] Force threshold value 1 / F_thresh val 1
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 8_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [N] 20000000.00 [N] 1000.00 [N]
p2175[0...n] Motor locked speed threshold / Mot lock n_thresh
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 120.00 [RPM]
p2175[0...n] Motor locked, velocity threshold / Mot lock v_thresh
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 1.20 [m/min]