Description: Sets the run-up time of the cooling system after a power-off command.
Description: Displays the control word for the cooling system.
Description: Sets the signal sources for the feedback signals from the cooling system.
Index: [0] = Cooling system powered-up
[1] = Cooling system ready to be powered-up
[2] = Cooling system, no alarm present
[3] = Cooling system, no fault present
[4] = Cooling system, no leaked liquid
[5] = Cooling system liquid flow OK
[6] = Cooling system, conductivity < fault threshold
[7] = Cooling system, conductivity < alarm threshold
p0264 Cooling system, run-on time / RKA run-on time
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9795
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [s] 180.0 [s] 30.0 [s]
r0265.0...3 BO: Cooling system, control word / RKA ctrl word
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power-up cooling system Power-up Deactivating -
01 Message, converter off Off On -
02 Acknowledge faults Acknowledgement No acknowledgement -
03 Leakage sensing OK No leaked liquid Leaked liquid -
p0266[0...7] BI: Cooling system, feedback signals, signal source / RKA fdbk S_src
A_INF (Cooling sys-
tem), B_INF (Cool-
ing system), SERVO
(Cooling system),
S_INF (Cooling sys-
tem), VECTOR
(Cooling system)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1