Parameters
List of parameters
1-144
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Set the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Notice: For VECTOR and SERVO, the following applies:
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is appropriately pre-
assigned. This is not the case when commissioning the motor (p0010 = 3).
Note: The parameter is automatically preset for motors from the motor list (p0301).
The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
Description: Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency: Refer to: p0329, p1980, p1981, p1982, p1983, r1984, r1985, r1987, p1990
Refer to: F07995
Notice: When the motor code (p0301) is changed, it is possible that p0325 is not pre-assigned.
p0325 can be pre-assigned using p0340 = 3.
Note: The value is automatically pre-assigned for the following events:
- For p0325 = 0 and automatic calculation of the closed-loop control parameters (p0340 = 1, 2, 3).
- for quick commissioning (p3900 = 1, 2, 3).
Description: Sets the correction factor for the stall torque/force at a 600 V DC link voltage.
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
p0323[0...n] Maximum motor current / Mot I_max
VECTOR Can be changed: C2(1, 3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 5722
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, FEM Expert list: 1
Min Max Factory setting
0.00 [Arms] 20000.00 [Arms] 0.00 [Arms]
p0325[0...n] Motor pole position identification current, 1st phase / Mot PolID I 1st ph
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Expert list: 1
Min Max Factory setting
0.000 [Arms] 10000.000 [Arms] 0.000 [Arms]
p0326[0...n] Motor stall torque correction factor / Mot M_stall_corr
SERVO Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: REL, FEM Expert list: 1
Min Max Factory setting
5 [%] 300 [%] 60 [%]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S Series and is the answer not in the manual?

Siemens SINAMICS S Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals