Description: Displays the first status word for monitoring functions.
Note: Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Description: Displays the second status word for monitoring functions.
Note: Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 07:
For servo drives, bit 07 is not used and is always inactive.
r2197.1...7 CO/BO: Status word monitoring 1 / ZSW monitor 1
SERVO (Lin) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2534
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 |v_act| < = velocity threshold value 2" Yes No 8010
02 |v_act| > velocity threshold value 2 Yes No 8010
03 n_act >= 0 Yes No 8010
06 |n_act| > n_max Yes No 8010
07 Velocity setpoint - actual value deviation in
tolerance t_off
Yes No 8010
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8010
05 n_set > 0 Yes No 8010
06 Motor locked Yes No 8012
07 Motor stalled Yes No 8012
10 Torque setpoint < torque threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013