List of parameters
Parameters
1-617
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the integral time (I component, integrating time constant) of the technology controller.
Note: p2285 = 0: The integral time is disabled.
Description: Sets the signal source for the pre-control signal of the technology controller.
Description: Sets the maximum limit of the technology controller.
Dependency: Refer to: p2292
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description: Sets the minimum limit of the technology controller.
Dependency: Refer to: p2291
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2285 Technology controller integral time / Tec_ctrl Tn
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2289[0...n] CI: Technology controller pre-control signal / Tec_ctrl prectrl
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_limit
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2292 CO: Technology controller minimum limiting / Tec_ctrl min_lim
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]