List of faults and alarms
Faults and Alarms
3-1521
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F06262 Infeed: Temperature switch in the line filter open when powering-up
Drive object: A_INF, S_INF
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY
Cause: When powering-up the infeed, the temperature in the line filter is too high. Powering-up is prevented.
Remedy: - ensure the correct and reliable connection of the line filter temperature switch with input X21 of the infeed.
- ensure the connection of the line filter specified for the infeed being used. Check the line filter type (p0220[0]).
- the filter temperature is too high. Allow the system to cool down.
- the internal fan of the filter module is defective. If required, replace the fan.
- defective temperature switch of the filter module. If required, replace the filter module.
F06300 Infeed: Line voltage too high at power on
Drive object: A_INF, B_INF, S_INF
Reaction: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The RMS line supply voltage Vrms was so high when powering-up that controlled operation is not possible without
exceeding the permissible maximum voltage in the DC link (p0280).
Fault condition: Vrms * 1.5 > p0280.
Fault value (r0949, floating point):
Lowest possible controlled DC link voltage for the line supply voltage presently connected.
See also: p0280 (DC link voltage maximum steady-state)
Remedy: - check the line supply voltage
- check the maximum DC link voltage and if required, increase (p0280).
- check the line supply voltage and compare with the actual line supply voltage (p0210).
- check whether the power unit is dimensioned for the line supply voltage actually being used.
See also: p0210 (Drive unit line supply voltage), p0280 (DC link voltage maximum steady-state)
A06301 (F) Infeed: Line supply overvoltage
Drive object: A_INF, B_INF, S_INF
Reaction: NONE
Acknowledge: NONE
Cause: The filtered (steady-state) value of the rms line supply voltage Vrms is higher than the alarm threshold (p0281).
Alarm condition: Vrms > p0281 * p0210.
Alarm value (r2124, floating point):
Actual steady-state line supply voltage.
See also: p0281 (Line supply overvoltage, warning threshold)
Remedy: - check the line supply.
- check the line supply voltage (p0210).
- check the alarm threshold (p0281).
See also: p0210 (Drive unit line supply voltage), p0281 (Line supply overvoltage, warning threshold)
Reaction upon F: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY (POWER ON)
F06310 (A) Infeed: Supply voltage (p0210) incorrectly parameterized
Drive object: A_INF, B_INF, S_INF
Reaction: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: After pre-charging was completed, the line supply voltage Vrms was calculated using the measured DC link voltage.
This voltage Vrms is not within the tolerance range of the supply voltage.
The following applies for the tolerance range: 85 % * p0210 < Vrms < 110 % * p0210.
Alarm value (r2124, floating point):
Line supply voltage Vrms present.
See also: p0210 (Drive unit line supply voltage)
Remedy: - check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
Reaction upon A: NONE
Acknowl. upon A: NONE