Parameters
List of parameters
1-150
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Notice: If p0338 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is appropriately pre-
assigned. This is not the case when commissioning the motor (p0010 = 3).
Note: The parameter is automatically preset for motors from the motor list (p0301).
Description: Displays the rated motor voltage
Note: For induction motors (p0300 = 1xx) the parameter is set to p0304.
For synchronous motors, parameter r0339 = p0304 is displayed. If p0304 = 0, then r0339 is calculated from p0305
and p0316.
Description: Setting to reset and automatically calculate filter and control (closed-loop) parameters.
Values: 0: No calculation
1: Complete re-calculation. of control parameters with COMM data
2: Reset control parameters
Notice: The following parameters are influenced using p0340:
p0340 = 1:
--> All of the parameters influenced for p0340 = 2
--> p3421 = p0223, p0225
--> p3422 = p0227
--> p3424 = p0225
--> p3415, p3425, p3555, p3614, p3620, p3622 are reset to the factory setting dependent on the particular unit.
p0340 = 2:
--> p3560, p3562, p3564, p3603, p3615 and p3617 are reset to the factory setting. For S_INF, these control param-
eters are not available
Note: When existing the quick commissioning using p3900 > 0, p0340 is automatically set to 1.
At the end of the calculations, p0340 is automatically set to 0.
Description: Setting to automatically calculate motor parameters and V/f open-loop and closed-loop control parameters from the
rating plate data.
r0339[0...n] Rated motor voltage / Mot V_rated
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p0340 Automatic calculation, control parameters / Calc auto par
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0
p0340[0...n] Automatic calculation of motor/control parameters / Calc auto par
SERVO, VECTOR Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 5 0