Function Diagrams
Vector control
2-1298
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-179 6495 – Excitation (FEM, p0300 = 5)
- 6495 -
Function diagram
87654321
fp_6495_51_eng.vsd
DO: VECTOR, VECTORGL, VECTORMV
SINAMICS
19.07.06 V02.05.00
Vector control - Excitation (FEM, p0300 = 5)
(1)
Excitation ready to be powered-up
p1645[0]
Control of the
excitation equipment for
separately-excited
synchronous motors (FEM)
[6495.7]
[6495.7]
[6495.7]
[6495.7]
[2610.2]
Excitation t_monit
2.0 ...1300.0 s
p1646 (20.0)
Excitation t_off
0.5 ...5.0 s
p1647 (0.8)
(1)
Excitation ready
p1645[1]
(1)
Excitation operational
p1645[2]
(1)
Excitation group signal fault
p1645[3]
(1)
Excitation group signal alarm
p1645[4]
(1)
Reserved
p1645[5..6]
1
2
3
7
Bit No.
0
Excitation ready feedback signal
Excitation ready to be powered-up,
feedback signal
Meaning
Excitation in operation feedback signal
Excitation group signal fault
Excitation group signal alarm
r1649.0
r1649
Excitation ZSW
r1649.2
r1649.3
r1649.7
r1649.1
To sequence control [2610]
Excitation status word
Bit No.
0 1 = Power-up excitation
Meaning
r1648.0
r1648
Excitation STW
Excitation control word
3
7
1 = Excitation, enable operation
1 = Excitation, acknowledge fault
r1648.3
r1648.7
To the excitation
1 1 = Excitation no OFF2 r1648.1
2 1 = Excitation no OFF3 r1648.2
10
1 = Master ctrl by excitation equipment
r1648.10
r1648.0
r1649.1
r1648.3
r1649.2
r0863.0
<1> For SINAMICS GL150: p1646[0] and p1646[1].
<2> Not for SINAMICS GL150.
<1> <2>
<2>