Description: Displays the number of motor pole pairs. The value is used for internal calculations.
Values:
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor
etc.
Dependency: For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated power (p0307), rated fre-
quency (p0310) and rated speed (p0311).
Refer to: p0307, p0310, p0311, p0314
Note: For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency
is zero.
Description: Sets the motor pole pair number.
Values:
p0314 = 1: 2-pole motor
p0314 = 2: 4-pole motor
etc.
Dependency: For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice: For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
Description: Sets the pole pair width of the linear motor.
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
r0313[0...n] Motor pole pair number, actual (or calculated) / Mot PolePairNo act
VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: MDS, p0130 Func. diagram: 5300
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
p0314[0...n] Motor pole pair number / Mot pole pair No.
SERVO, VECTOR Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Unsigned8 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 127 0
p0315[0...n] Motor pole pair width / MotPolePair width
SERVO (Lin) Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1.00 [mm] 1000.00 [mm] 30.00 [mm]