Parameters
List of parameters
1-246
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: For VECTOR, the following applies:
The "flying restart" function should be activated (p1200) when changing-over to a motor that is already running.
Re bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate
motor data sets.
Re bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
Description: Sets the configuration for the motor and encoder changeover.
Note: For VECTOR, the following applies:
The "flying restart" function should be activated (p1200) when changing-over to a motor that is already running.
Re bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate
motor data sets.
Re bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
Description: Displays the status word for the motor data set changeover.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Contactor changeover from the applica-
tion/drive
application Drive -
01 Pulse cancelation by application/drive application Drive -
02 Suppress drive parking for EDS changeover Yes No -
p0833 Data set changeover configuration / DS_chng config
VECTOR Can be changed: C2(15), U Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Contactor changeover from the applica-
tion/drive
application Drive -
01 Pulse cancelation by application/drive application Drive -
02 Suppress drive parking for EDS changeover Yes No -
r0835.0 CO/BO: Motor data set changeover status word / MDS_chngov ZSW
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor data set changeover active Active Not active 8575