List of parameters
Parameters
1-821
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the sampling time for the inputs and outputs of the Terminal Board 30 (TB30).
Index: [0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency: The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (r0110, r0111).
Refer to: p0009, r0110, r0111
Note: The modified sampling time is not effective until the drive unit is powered-up again.
For clock cycle synchronous PROFIBUS operation, the TB30 hardware (e.g. A/D converter ) is operated with the
PROFIBUS clock cycle (r2064[1]). This clock cycle is also kept after the PROFIBUS connection has been exited up
to the next time that the Control Unit is powered-down. In this case, a faster sampling time than the PROFIBUS
clock cycle is not practical in p4099[0...2].
Description: Sets the sampling time for the inputs and outputs of terminal module 31 (TM31).
Index: [0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency: The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (r0110, r0111).
Refer to: p0009, r0110, r0111
Notice: The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Note: - the modified sampling time is not effective until the drive unit is powered-up again.
- P4099(0) must never equal zero.
p4099[0...2] TB30 inputs/outputs, sampling time / TB30 I/O t_sample
TB30 Can be changed: C1(3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9100, 9102,
9104, 9106
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] [0] 4000.00 [µs]
[1] 4000.00 [µs]
[2] 4000.00 [µs]
p4099[0...2] TM31 inputs/outputs, sampling time / TM31 I/O t_sample
TM31 Can be changed: C1(3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9550
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] 4000.00 [µs]