Faults and Alarms
List of faults and alarms
3-1522
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F06310 (A) Supply voltage (p0210) incorrectly parameterized
Drive object: SERVO
Reaction: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: For AC/AC drive units, the measured DC voltage lies outside the tolerance range after pre-charging has been com-
pleted. The following applies for the tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210.
See also: p0210 (Drive unit line supply voltage)
Remedy: - check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
Reaction upon A: NONE
Acknowl. upon A: NONE
F06310 (A) Supply voltage (p0210) incorrectly parameterized
Drive object: VECTOR
Reaction: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: For AC/AC drive units, the measured DC voltage lies outside the tolerance range after pre-charging has been com-
pleted: 1.16 * p0210 < r0070 < 1.6 * p0210.
See also: p0210 (Drive unit line supply voltage)
Remedy: - check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
Reaction upon A: NONE
Acknowl. upon A: NONE
F06311 Infeed: Supply voltage (p0210) fault
Drive object: A_INF, B_INF, S_INF
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: After pre-charging was completed, the line supply voltage Vrms was calculated using the measured DC link voltage.
This voltage Vrms does not lie within the extended permissible tolerance range of the line supply voltage for 230 V
applications.
The following applies for the tolerance range: 75 % * p0210 < Vrms < 120 % * p0210.
Alarm value (r2124, floating point):
Line supply voltage Vrms present.
See also: p0210 (Drive unit line supply voltage)
Remedy: - check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
F06320 Master/slave: Multiplexer control not valid
Drive object: A_INF
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: Values 0, 1, 2 and 3 are valid to control the multiplexer via CI: 3572. In this case, an invalid value was identified. The
control remains effective with the previous value.
Fault value (r0949, interpret decimal):
Invalid value to control the multiplexer.
See also: p3572 (Master/slave active current setpoint, multiplexer selection)
Remedy: - check the interconnection to control the multiplexer (CI: p3572).
- check the signal source signal value of the BICO interconnection.
See also: p3572 (Master/slave active current setpoint, multiplexer selection)