List of faults and alarms
Faults and Alarms
3-1511
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F03500 (A) TM: Initialization
Drive object: All objects
Reaction: OFF1 (OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: When initializing the Terminal Modules, the terminals of the Control Unit or the Terminal Board 30, an internal soft-
ware error has occurred.
Fault value (r0949, interpret decimal):
The thousands location = 1 ... 3:
The component number (p0151) of the module involved is specified at the ones, tens and hundreds position.
Remedy: - power-down the power supply for the Control Unit and power-up again.
- check the DRIVE-CLiQ connection.
- if required, replace the Terminal Module.
The Terminal Module should be directly connected to a DRIVE-CLiQ socket of the Control Unit.
If the fault occurs again, replace the Terminal Module.
Reaction upon A: NONE
Acknowl. upon A: NONE
A03501 TM: Sampling time change
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The sampling times of the inputs/outputs were changed.
This change only becomes valid after the next boot.
Remedy: Carry out a POWER ON.
F03505 (N, A) TM: Analog input wire breakage
Drive object: All objects
Reaction: OFF1 (OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The input current of the Terminal Module analog input has exceeded the threshold value parameterized in p4061[x].
This fault can only occur, if p4056[x] = 3 (4 ... 20 mA with monitoring) is set.
Index x = 0: Analog input 0 (X522.1 to .3)
Index x = 1: Analog input 1 (X522.4 to .5)
Fault value (r0949, interpret decimal):
The component number (p0151) of the module involved is specified at the ones, tens and hundreds position.
The thousands position specifies the analog input involved: 0: Analog input 0 (AI 0), 1: Analog input 1 (AI 1)
Remedy: Check the connection to the signal source for interruptions.
Check the magnitude of the impressed current - it is possible that the impressed signal is too low.
Please note that the input has a load resistor of 250 Ohm.
The input current measured by the Terminal Module can be read-out of r4052[x].
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
A03506 (F, N) 24 V power supply missing
Drive object: A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The 24 V power supply for the digital outputs (X124) is missing.
Remedy: Check the terminals for the power supply voltage (X124, L1+, M).
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE