Parameters
List of parameters
1-288
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
Description: Displays those parameters with a value other than the factory setting for this drive.
Dependency: Refer to: r0990, r0991
Note: Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list completely comprises the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
Description: Runs the appropriate ACX file on the CompactFlash card.
The Connector Inputs (CI) for the speed setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected ACX file must be located in the following directory:
... /PMACROS/<drive object>/P1000/PMxxxxxx.ACX
Example:
p1000 = 6 --> the file PM000006.ACX is run.
Dependency: The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash card.
Refer to: p0015, p0700, p1500, r8572
Notice: No errors were issued during fast commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
Note: The macros in the specified directory are displayed in r8572. r8572 is not in the Expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
r0999[0...99] List of modified parameters 10 / List chang. par 10
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, DMC20,
SERVO, S_INF,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 0
Min Max Factory setting
- - -
p1000[0...n] Macro Connector Inputs (CI) for speed setpoints / Macro CI n_set
SERVO, VECTOR Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 999999 0