List of parameters
Parameters
1-201
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Caution: After changing over the technological application and then calculating the open-loop and closed-loop parameters,
the behavior of the motor can have changed very significantly (e.g. the same setpoint results in a higher speed due
to a different reference speed). For this reason extreme caution must be taken when the motor is started for the first
time.
Note: The calculation of parameters, dependent on the technological application can be called-up as follows:
- when exiting the quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
- when writing p0578 = 1
For p0500 = 100 and the calculation is initiated, the following parameters are set:
- p1520/p1521 = rated motor torque (r0333)
- p1530/p1531= 2*pi*r0333*p0311 (rotary) or r0333*p0311 (linear)
- p2000 = rated motor speed (p0311)
- p2175 = factory setting
- p2177 = factory setting
For p0500 = 101 and the calculation is initiated, the following parameters are set:
- p1520/p1521 = torque at the maximum motor current (p0323)
- p1530/p1531= power at the maximum motor current (p0323) and rated motor speed (p0311)
- p2000 = rated motor speed (p0311)
- p2175 = maximum value
- p2177 = 0.2 s
For p0500 = 102 and the calculation is initiated, the following parameters are set:
- p1520/p1521 = rated motor torque (r0333)
- p1530/p1531= 2*pi*r0333*p0311 (rotary) or r0333*p0311 (linear)
- p2000 = maximum motor speed (p0322) if p0322 is not equal to 0, otherwise rated motor speed (p0311)
- p2175 = factory setting
- p2177 = factory setting
Description: Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0578.
Values: 0: Standard drive (VECTOR)
1: Pumps and fans
Dependency: Refer to: p2175, p2177
Caution: After changing over the technological application and then calculating the open-loop and closed-loop parameters,
the behavior of the motor can have changed very significantly (e.g. the same setpoint results in a higher speed due
to a different reference speed). For this reason extreme caution must be taken when the motor is started for the first
time.
Note: The calculation of parameters, dependent on the technological application can be called-up as follows:
- when exiting the quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
- when writing p0578 = 1
p0500 Technology application / Techn application
VECTOR Can be changed: C2(1, 5), T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Applications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 1