Parameters
List of parameters
1-588
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p2161, r2197, r2199
Description: Sets the hysteresis velocity (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency: Refer to: p2161, r2197, r2199
Description: Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency: Refer to: r2197, r2198, r2199
Description: Sets the signal source for the velocity setpoint for the following messages:
"Velocity setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|v_set| < p2161" (BO: r2198.4)
"v_set > 0" (BO: r2198.5)
Dependency: Refer to: r2197, r2198, r2199
p2150[0...n] Hysteresis velocity 3 / v_hysteresis 3
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 3.00 [m/min] 0.02 [m/min]
p2151[0...n] CI: Speed setpoint for messages/signals / n_set for msg
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 8010
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1438[0]
p2151[0...n] CI: Velocity setpoint for messages/signals / v_set for msg
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 8010
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1438[0]