List of faults and alarms
Faults and Alarms
3-1445
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Reaction upon F: A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
A01049 CU CompactFlash: It is not possible write to file
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: It is not possible to write into a write-protective file (PSxxxxxx.acx). The write request was interrupted.
Alarm value (r2124, interpret decimal):
Drive object number.
Remedy: Check whether the "write protected" attribute has been set for the files on the CompactFlash card under
.../USER/SINAMICS/DATA/... When required, remove write protection and save again (e.g. set p0971 to 1).
F01050 CompactFlash card and device not compatible
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (NONE, OFF1, OFF3)
VECTOR: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: The CompactFlash card and the device type do not match (e.g. a CompactFlash card for SINAMICS S is inserted in
SINAMICS G).
Remedy: - insert the matching CompactFlash card
- use the matching Control Unit or power unit.
F01051 Drive object type is not available
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The drive object type in conjunction with the selected application-specific perspective is not available. The required
descriptive file (PDxxxyyy.ACX) does not exist on the CompactFlash card.
Fault value (r0949, interpret decimal):
Index of p0103 and p0107.
See also: p0103 (Application-specific view), r0103 (Application-specific view), p0107 (Drive object type), r0107
(Drive object type)
Remedy: - for this drive object type (p0107), select a valid application-specific perspective (p0103).
- save the required descriptive file (PDxxxyyy.ACX) on the CompactFlash card.
See also: p0103 (Application-specific view), r0103 (Application-specific view), p0107 (Drive object type), r0107
(Drive object type)
A01052 CU: System overload calculated for the complete target topology
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A system overload was calculated based on a complete active target topology.
Alarm value (r2124, interpret decimal):
2: Computation time load too high.
6: Cyclic computation time load too high.
Remedy: - reduce the sampling time.
- only use one data set (CDS, DDS).
- de-activate the function module.
- de-activate the drive object.
- remove the drive object from the target topology.
Note:
After executing the appropriate counter-measure, a new calculation must be initiated with p9974 = 1.