Parameters
List of parameters
1-680
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
The following applies: Reference frequency (in Hz) = reference velocity (in (m/min) / 60)
Dependency: Refer to: p2000
Note: This parameter represents the numerical value of the reference quantity in the currently selected units and is only
available for interconnection with Drive Control Chart (DCC).
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
Example 1:
The signal of an analog input (e.g. r4055[0]) is connected to a velocity setpoint (e.g. p1070[0]). The actual percent-
age input value is cyclically converted into the absolute velocity setpoint using the reference velocity (p2000).
Example 2:
The setpoint from PROFIBUS (r2050[1]) is connected to a velocity setpoint (e.g. p1070[0]). The current input value
is cyclically converted into a percentage value via the pre-specified normalization 4000 hex. This percentage value
is converted to the absolute velocity setpoint via reference velocity (p2000).
Description: Displays the actual reference quantity for voltages.
All voltages specified as relative value are referred to this reference quantity. The reference quantity in this param-
eter corresponds to 100% or 4000 hex or 4000 0000 hex.
Dependency: Refer to: p2001
Note: This parameter represents the numerical value of the reference quantity in the currently selected units and is only
available for interconnection with Drive Control Chart (DCC).
Description: Displays the actual reference quantity for currents.
All currents specified as relative value are referred to this reference quantity. The reference quantity in this parame-
ter corresponds to 100% or 4000 hex or 4000 0000 hex.
Dependency: Refer to: p2002
Note: This parameter represents the numerical value of the reference quantity in the currently selected units and is only
available for interconnection with Drive Control Chart (DCC).
Description: Displays the actual reference quantity for torque (r0108.12 = 0) or force (r0108.12 = 1).
All torques specified as relative value are referred to this reference quantity. The reference quantity in this parame-
ter corresponds to 100% or 4000 hex or 4000 0000 hex.
r2701 CO: Reference voltage actual / Ref voltage act
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
r2702 CO: Reference current actual / Ref current act
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
r2703 CO: Reference torque actual / Ref torque act
SERVO, TM41, VEC-
TOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -