PROFIdrive
Function Diagrams
2-1183
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-75 2487 – IF2 send telegram, free interconnection via BICO (p0922 = 999)
- 2487 -
Function diagram
87654321
fp_2487_01_eng.vsd
DO: SERVO, VECTOR
SINAMICS S
28.06.07 V02.05.01
PROFIdrive - IF2 send telegram, free interconnection via BICO (p0922 = 999)
IF2 Diag send Wort 1...16
r8853[0...15]
...
PZD send word 1
PZD send word 2
DWORD
p8861[0]
DWORD
p8861[1]
DWORD
p8861[2]
DWORD
p8861[3]
DWORD
p8861[4]
DWORD
p8861[5]
DWORD
p8861[6]
DWORD
p8861[7]
PZD send word 3
PZD send word 4
PZD send word 5
PZD send word 6
PZD send word 7
PZD send word 8
<2>
(0)0
p8851[1]
(0)0
p8851[2]
(0)0
p8851[3]
(0)0
p8851[4]
(0)0
p8851[5]
(0)0
p8851[6]
(0)0
p8851[7]
(0)0
p8851[8]
(0)0
p8851[0]
<2>
Reference quantities for
further interconnection
p880x
<3>
<1>
r8863[0...14]
PROFIdrive send
telegram
PROFIBUS
PROFINET
Drive object n
Header
Drive object 1
Drive object 2
.
.
.
.
.
.
Drive object m
Trailer
<1> To comply with the PROFIdrive profile, send word 1 must be used as status word 1
(ZSW1), not as DWORD.
<2> Every PZD word can be assigned a word or a double word. Only one of the 2
interconnection parameters p8851 or p8861 may have a value
0 for a PZD word.
<3> Physical word and double word values are inserted in the telegram as referenced
variables. p880x apply as reference variables (telegram contents = 4000 hex or 4000
0000 hex in the case of double words, if the input variable has the value p880x).
The following applies for temperature values: 100 °C -> 100 % = 4000 hex; 0 °C -> 0%
= 4000 0000 hex.
<4> The number of PZD send words depends on the drive object type.