Siemens SINAMICS S Series - p1619[0...n] Setpoint;actual value tracking threshold; SetAct track thrsh; p1620[0...n] Stator current, minimum; I_stator min; p1621[0...n] Changeover speed, inner cos phi = 1; n_chngov cos phi=1; p1622[0...n] Field-generating current setpoint smoothing time constant; Id_setp T_smth

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-454
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Threshold for setpoint - actual value tracking of the stator current in the q direction of the current model.
Description: Sets the minimum stator current for separately-excited synchronous motors (FEM).
A negative value means that the field-generating stator current (d-axis) has a negative sign. The valid value is inter-
nally limited to 50% of the rated motor current (p0305).
Description: Sets the speed where a change is made from the inner to the outer cos phi = 1.
If the value that is entered exceeds the rated speed, then a change is made to the inner cos phi = 1 over the com-
plete speed range.
Description: Sets the smoothing time constant for the setpoint of the field-generating current components.
The current filtered in this way is included in the calculation of the cos phi.
Description: Displays the steady-state field generating current setpoint (Id_set).
p1619[0...n] Setpoint/actual value tracking threshold / SetAct track thrsh
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p1620[0...n] Stator current, minimum / I_stator min
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
-10000.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p1621[0...n] Changeover speed, inner cos phi = 1 / n_chngov cos phi=1
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 0.00 [RPM]
p1622[0...n] Field-generating current setpoint smoothing time constant / Id_setp T_smth
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.1 [ms] 200.0 [ms] 20.0 [ms]
r1623 Field-generating current setpoint (steady-state) / Id_set stationary
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6723
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]