Description: Sets the sensor to monitor the motor temperature.
Values: 0: No sensor
1: Temperature sensor via encoder 1
2: Temperature sensor via encoder 2
3: Temperature sensor via encoder 3
10: Temperature sensor via a BICO interconnection
11: Temperature sensor via Motor Module
Dependency: Refer to: r0458, p0601, p0603
Caution: If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another
encoder, then then the temperature adaptation of the motor resistances must be switched-out. Otherwise, in con-
trolled-loop operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice: The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
Note: Re p0600 = 10:
The BICO interconnection should be executed via connector input CI: p0603.
Re p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is con-
nected at the adapter (X210).
Description: Sets the sensor to monitor the motor temperature.
Values: 0: No sensor
1: Temperature sensor via encoder 1
2: Temperature sensor via encoder 2
3: Temperature sensor via encoder 3
10: Temperature sensor via a BICO interconnection
11: Temperature sensor via Motor Module
Dependency: Refer to: r0458, p0601, p0603
Caution: If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another
encoder, then then the temperature adaptation of the motor resistances must be switched-out. Otherwise, in con-
trolled-loop operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice: The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
Note: Re p0600 = 10:
The BICO interconnection should be executed via connector input CI: p0603.
Re p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is con-
nected at the adapter (X210).
p0600[0...n] Motor temperature sensor for monitoring / Mot temp_sensor
SERVO Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 11 1
p0600[0...n] Motor temperature sensor for monitoring / Mot temp_sensor
VECTOR Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 11 0