Description: Sets the alarm threshold for the change of the capacitance of the line filter.
The monitoring of the filter capacitance is de-activated with p3676 = 0.00 %.
Dependency: Refer to: p3670
Refer to: A06250
Note: Prerequisites for monitoring the filter capacitance:
The phase currents must be measured at two capacitors of the line filter. To do this, CTs should be connected at
the 10 V inputs of the VSM.
Description: Displays the capacitance of the line filter (for a star circuit configuration).
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
Dependency: Refer to: p3676
Note: Prerequisite:
The monitoring of the filter capacitance is activated.
Description: Sets the signal source to inhibit the internal Braking Module.
1 signal: The Braking Module is inhibited.
0 signal: The Braking Module is enabled.
Dependency: Refer to: A06904
Caution: When the Braking Module is inhibited, no energy can be dissipated in the braking resistor.
p3676 VSM line filter capacitance alarm threshold / VSMfilt C A_thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 0.00 [%]
r3677[0...2] VSM line filter capacitance / VSM filt C
A_INF, S_INF Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [µF] - [µF] - [µF]
p3680 BI: Braking Module internal inhibit / BM int inhib
B_INF Can be changed: T Calculated: - Access level: 4
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0