Siemens SINAMICS S Series - p3676 VSM line filter capacitance alarm threshold; VSMfilt C A_thresh; r3677[0...2] VSM line filter capacitance; VSM filt C; p3680 BI: Braking Module internal inhibit; BM int inhib

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-731
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the alarm threshold for the change of the capacitance of the line filter.
The monitoring of the filter capacitance is de-activated with p3676 = 0.00 %.
Dependency: Refer to: p3670
Refer to: A06250
Note: Prerequisites for monitoring the filter capacitance:
The phase currents must be measured at two capacitors of the line filter. To do this, CTs should be connected at
the 10 V inputs of the VSM.
Description: Displays the capacitance of the line filter (for a star circuit configuration).
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
Dependency: Refer to: p3676
Note: Prerequisite:
The monitoring of the filter capacitance is activated.
Description: Sets the signal source to inhibit the internal Braking Module.
1 signal: The Braking Module is inhibited.
0 signal: The Braking Module is enabled.
Dependency: Refer to: A06904
Caution: When the Braking Module is inhibited, no energy can be dissipated in the braking resistor.
p3676 VSM line filter capacitance alarm threshold / VSMfilt C A_thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 0.00 [%]
r3677[0...2] VSM line filter capacitance / VSM filt C
A_INF, S_INF Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [µF] - [µF] - [µF]
p3680 BI: Braking Module internal inhibit / BM int inhib
B_INF Can be changed: T Calculated: - Access level: 4
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0