Parameters
List of parameters
1-464
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Note: For an extended general 2nd order filter, by inserting the same natural frequency in both the numerator and in the
denominator, i.e. bandstop frequency, a bandstop filter is implemented. If the numerator damping of zero is
selected, the bandstop frequency is completely suppressed. The denominator damping can be determined from the
equation for the 3 dB bandwidth: f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
Description: Sets the denominator natural frequency for current setpoint filter 2 (PT2, general filter).
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Description: Sets the denominator damping for current setpoint filter 2.
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Description: Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Description: Sets the numerator damping for current setpoint filter 2.
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
p1663[0...n] Current setpoint filter 2 denominator natural frequency / I_set_filt 2 fn_n
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.5 [Hz] 16000.0 [Hz] 1999.0 [Hz]
p1664[0...n] Current setpoint filter 2 denominator damping / I_set_filt 2 D_n
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.001 10.000 0.700
p1665[0...n] Current setpoint filter 2 numerator natural frequency / I_set_filt 2 fn_z
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.5 [Hz] 16000.0 [Hz] 1999.0 [Hz]
p1666[0...n] Current setpoint filter 2 numerator damping / I_set_filt 2 D_z
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.000 10.000 0.700