List of parameters
Parameters
1-119
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the total DC link capacitance.
Note: The total DC link capacitance of a DC link group comprises the sum of the sub-capacitances of all motor/infeed
modules and the additional DC link capacitors.
Description: Sets the type of the filter at the motor side.
Values: 0: No filter
1: Motor reactor
2: du/dt filter
3: Sinusoidal filter, Siemens
4: Sinusoidal filter, third-party
Dependency: The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
p0230 = 3:
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sinusoidal filter capacitance) = filter capacitance
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
--> p1802 (modulator modes) = space vector modulation without overcontrol
p0230 = 4:
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1802 (modulator modes) = space vector modulation without overcontrol
The user must set the following parameters according to the data sheet of the sinusoidal filter and also the user
must check whether they are permitted.
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sinusoidal filter capacitance) = filter capacitance
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note: if a filter type cannot be selected, then this filter type is not permitted for the Motor Module.
p0230 = 2:
Chassis-type power units with du/dt filter, depending on the rated pulse frequency, may only be operated with a
maximum pulse frequency of p1800 = 2.5 kHz or 4 kHz. The output frequency is limited to 150 Hz.
p0230 = 3:
Sinusoidal filters with a rated pulse frequency of 1.25 or 2.5 kHz should only be operated with a current controller
sampling rate p0115[0] = 400 µs, sinusoidal filters with a rated pulses frequency of 2 or 4 kHz with p0115[0] = 250
µs.
The sinusoidal filter cannot be selected if the current controller sampling rate hasn't been appropriately set.
p0227 Infeed, DC-link capacitance, power unit / INF C
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.20 [mF] 1000.00 [mF] 1.00 [mF]
p0230 Drive filter type, motor side / Drv filt type
VECTOR Can be changed: C2(1, 2) Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 0