Parameters
List of parameters
1-982
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the delay time for the SLS changeover or for the changeover from SLS to SOS for the function "Safely Limited
Speed" (SLS).
When transitioning from a higher to a lower safely-limited velocity/speed stage or to the safe operating stop (SOS),
within this delay time, the "old" velocity stage remains active.
Even if SLS or SOS is activated from non safety-related operation, then this delay is still applied.
Dependency: Refer to: p9551
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SLS: Safely Limited Speed
SOS: Safe Operating Stop
Description: Sets the transition time from STOP C to "safe operating stop" (SOS).
Dependency: Refer to: p9552
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SOS: Safe Operational Stop
Description: Sets the transition time from STOP D to "safe operating stop" (SOS).
Dependency: Refer to: p9553
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SOS: Safe Operating Stop
p9351 SI Motion SLS changeover delay time (Motor Module) / SI Mtn SLS t MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2825
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9352 SI Motion transition time STOP C to SOS (Motor Module) / SI Mtn t C->SOS MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2825
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9353 SI Motion transition time STOP D to SOS (Motor Module) / SI Mtn t D->SOS MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2825
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]