Parameters
List of parameters
1-786
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for terminal DI/DO 10 (X541.4) of terminal module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.10 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 2 (X521.3) of terminal module 41 (TM41).
Note: Prerequisite: The DI/DO must be set as an output (p4028.10 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 10 (X521.4) of terminal module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.10 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 11 (X541.5) of terminal module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.11 = 1).
DI/DO: Bidirectional Digital Input/Output
p4040 BI: TM31 signal source for terminal DI/DO 10 / TM31 S_src DI/DO10
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p4040 BI: TM41 signal source for terminal DI/DO 2 / TM41 S_src DI/DO 2
TM41 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9662
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p4040 BI: TM15DI/DO signal source for terminal DI/DO 10 / TM15D S_srcDI/DO10
TM15DI_DO Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9401
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p4041 BI: TM31 signal source for terminal DI/DO 11 / TM31 S_src DI/DO11
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 1840, 9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0