Siemens SINAMICS S Series - C01714 SI Motion CU: Safely-Limited Speed exceeded

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of faults and alarms
3-1492
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Re fault value = 1005:
- check the conditions for pulse enable.
Re fault value = 1011:
- for diagnostics, refer to parameter (r9571).
Re fault value = 1012:
- upgrade the Sensor Module software.
Re fault value = 1020, 1021:
- check the communication link.
- carry out a POWER ON (power off/on) for all components.
- replace the hardware.
Re fault value = 5000, 5014, 5023, 5024, 5030, 5031, 5032, 5042, 5043, 5052, 5053, 5068, 5072, 5073, 5082 ...
5087, 5090, 5091, 5122 ... 5125, 5132 ... 5135, 5140:
- carry out a POWER ON (power off/on) for all components.
- check whether there is a DRIVE-CLiQ communications error between the Control Unit and the Motor Module
involved and if required, carry out a diagnostics routine for the faults identified.
- upgrade the firmware release.
- contact the Hotline.
- replace the Control Unit.
Re fault value = 5012:
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Module (p9810). It is
not permissible that the PROFIsafe address is 0 or FFFF!
Re fault value = 5013, 5025:
- carry out a POWER ON (power off/on) for all components.
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Module (p9810).
- check whether there is a DRIVE-CLiQ communications error between the Control Unit and the Motor Module
involved and if required, carry out a diagnostics routine for the faults identified.
Re fault value = 5022:
- check the setting of the values of the F parameters at the PROFIsafe slave (F_SIL, F_CRC_Length,
F_Par_Version, F_Source_Add, F_Dest_add, F_WD_Time).
Re fault value = 5026:
- check the settings of the values of the F parameters and the F-parameter-CRC (CRC1) calculated from these at
the PROFIsafe slave and update.
Re fault value = 5065:
- check the configuration and communication at the PROFIsafe slave (Cons. No. / CRC).
- check whether there is a DRIVE-CLiQ communications error between the Control Unit and the Motor Module
involved and if required, carry out a diagnostics routine for the faults identified.
Re fault value = 5066:
- check the setting of the F parameter value of the time monitoring at the PROFIsafe-slave and, if required, increase
the timeout value (F_WD_Time).
This message can be acknowledged as follows:
- motion monitoring functions integrated in the drive: Via Terminal Module 54F (TM54F) or PROFIsafe
- motion monitoring functions with SINUMERIK: Via the machine control panel
See also: p9300 (SI motion monitoring clock cycle (Motor Module)), p9500 (SI motion monitoring clock cycle (Control
Unit))
C01714 SI Motion CU: Safely-Limited Speed exceeded
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive had moved faster than that specified by the velocity limit value (p9531). The drive is stopped as a result of
the configured stop response (p9563).
Message value (r9749, interpret decimal):
100: SLS1 exceeded.
200: SLS2 exceeded.
300: SLS3 exceeded.
400: SLS4 exceeded.
1000: Encoder limit frequency exceeded.