Parameters
List of parameters
1-278
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
r0964[6] = 600 --> second part, firmware version (complete version: V01.02.06.00)
Description: Displays the PROFIdrive profile number and profile version. Constant value = 0303 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 03 hex = Version 3
Description: Displays the system runtime in ms since the last POWER ON.
Note: The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
Description: The parameter is used to initiate that the parameters of an individual infeed unit are reset.
The parameters of the basic commissioning (refer to p0009) are in this case not reset (p0107, p0108, p0121,
p0170). These can only be reset using the factory setting of the complete drive unit (p0976).
The sampling times (p0111, p0112, p0115) are only not reset if this results in a conflict with the basic clock cycle
(p0110).
Values: 0: Inactive
1: Starts a parameter reset
100: Starts a BICO interconnection reset
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate that the parameters of an individual drive unit are reset.
r0965 PROFIdrive profile number / PD profile number
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
p0969 System runtime relative / t_System relative
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 1750, 8060
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 4294967295 [ms] 0 [ms]
p0970 Reset infeed parameter / INF par reset
A_INF, B_INF,
S_INF
Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 100 0
p0970 Reset drive parameters / Drive par reset
SERVO, VECTOR Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 100 0