List of parameters
Parameters
1-583
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the system runtime in days when the fault was removed.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2114, r2130, r2133
Notice: The time comprises r2136 (days) and r2109 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the control word of the faults and alarms.
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description: Displays the first status word of faults and alarms.
Note: Re bit 03, 05, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present"/"alarm present" has occurred, a change
in the buffer was also detected (r0944, r9744, r2121).
r2136[0...63] Fault time removed in days / t_flt resolv. days
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 8060
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
All objects Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2546
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes (0/1 edge) No -
10 External alarm 1 (A07850) No Yes (1/0 edge) -
11 External alarm 2 (A07851) No Yes (1/0 edge) -
12 External alarm 3 (A07852) No Yes (1/0 edge) -
13 External fault 1 (F07860) No Yes (1/0 edge) -
14 External fault 2 (F07861) No Yes (1/0 edge) -
15 External fault 3 (F07862) No Yes (1/0 edge) -
r2139.0...8 CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
All objects Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2548
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ackn. running Yes No -
03 Fault present Yes No -
05 Safety message present Yes No -
06 Internal message 1 present Yes No -
07 Alarm present Yes No -
08 Internal message 2 present Yes No -