List of parameters
Parameters
1-601
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the delay time to evaluate the load monitoring.
Description: Sets the torque/force threshold value for the signal "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: r0033, p2195, r2199
Description: Sets the torque/force threshold value for the signal "Torque/force utilization < torque/force threshold value 2" (BO:
r2199.11).
The message "torque/force setpoint < p2174" (BO: r2198.10) and "torque/force utilization < p2194" (BO: r2199.11)
are only evaluated after the run-up and the delay time has expired.
Dependency: Refer to: r0033, p2195, r2199
p2190[0...n] Load monitoring force threshold 3, lower / M_thresh 3 lower
SERVO (Extended
msg, Lin)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: 8_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [N] 100000.00 [N] 0.00 [N]
p2192[0...n] Load monitoring delay time / Load monit t_del
SERVO (Extended
msg), VECTOR
(Extended msg)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [s] 65.00 [s] 10.00 [s]
p2194[0...n] Torque threshold value 2 / M_thresh val 2
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 90.00 [%]
p2194[0...n] Force threshold value 2 / F_thresh val 2
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 90.00 [%]