Overviews
Function Diagrams
2-1125
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-23 1780 – Terminal Module 15 (TM15)
- 1780 -
Function diagram
87654321
fp_1780_51_eng.vsd
DO: TM15
SINAMICS
12.06.06 V02.05.00
Overviews - Terminal Module 15 (TM15)
p4099 (125.00 µs)
<2> The plug-in connections X520, X521 and X522 have to be coded
according to the specifications in the relevant technical
documentation.
DRIVE-CLiQ socket 0
X500
DRIVE-CLiQ socket 1
X501
L3+
M3
+ 24 V
M
M
=
~
+M
+24 V DC
To the next
device
X524
M
+
M
+
X520
1
2
3
4
5
6
7
8
L1+
DI/DO 0
DI/DO 1
DI/DO 2
DI/DO 3
DI/DO 4
DI/DO 5
DI/DO 6
10
DI/DO 7
M1
9
L1+
1
0
r4304.0
r4204.0
p4028.0
1
0
p4028.7
r4304.7
r4204.7
...
1
0
r4304.8
r4204.8
p4028.8
1
0
p4028.15
r4304.15
r4204.15
... ... ...
1
0
r4305.0
r4205.0
p4028.10
1
0
p4028.15
r4305.7
r4205.7
... ... ...
...
<1>
...
M1
X521
1
2
3
4
5
6
7
8
L2+
DI/DO 8
DI/DO 9
DI/DO 10
10
M2
9
<1>
...
L2+
DI/DO 11
DI/DO 12
DI/DO 13
DI/DO 14
DI/DO 15
M2
X522
1
2
3
4
5
6
7
8
L3+
DI/DO 16
DI/DO 17
DI/DO 18
10
M3
9
<1>
...
DI/DO 19
DI/DO 20
DI/DO 21
DI/DO 22
DI/DO 23
...
<1> The wiring shown dashed applies for the setting as
digital output (p4028.x = 1).
<2>
<2>
<2>
+ 24 V