Parameters
List of parameters
1-40
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 41 (TM41).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
4: Encoder commissioning
5: Technological application/units
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 17 (TM17).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 15 (TM15).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
p0010 TM41 commissioning parameter filter / TM41 comm par_filt
TM41 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0
p0010 TM17 commissioning parameter filter / TM17 comm par_filt
TM17 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0
p0010 TM15 commissioning parameter filter / TM15 comm par_filt
TM15 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0