Parameters
List of parameters
1-992
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: Set connection to 0
1: Set connection to 1 (100 %)
2: Set connection to factory setting
15: Finished
Dependency: Refer to: r9490, r9491, r9492
Note: All indices of r9491 to p9493 designate the same interconnection.
r9491[x] contains the signal receiver and r9492[x] the matching signal source; p9493[x] can be set to modify the
interconnection.
Description: Setting for the behavior for BICO interconnections to other non-operational/de-activated drive objects.
If this drive object has BICO interconnections to other non-operational or de-activated drive objects as drain, then
using these parameters, all of the associated BI/CI parameters of this drive object can be marked and then set to
the factory setting or only marked.
Values: 0: Do not do anything
1: Mark connection
2: Mark connection and then set to the factory setting
Dependency: Refer to: p9496, p9497, r9498, r9499
Refer to: A01318, A01507
Note: The BI/CI parameters involved are listed in r9498[0...29] (drain).
The associated BO/CO parameters are listed in r9499[0...29] (source).
However, r9498 and r9499 are only then filled if p9495 is not equal to 0, otherwise they remain empty.
Description: If this drive object has BICO interconnections to other drive objects that are either not operational or have been de-
activated, then using this parameter, all of the BI/CI parameters involved with this drive object can be re-estab-
lished.
Values: 0: Do not do anything
1: Restore the connections from the list
2: Delete the connection from the list
Dependency: Refer to: p9495, p9497, r9498, r9499
Refer to: A01318, A01507
Note: The BI/CI parameters involved are listed in r9498[0...29] (drain).
The associated BO/CO parameters are listed in r9499[0...29] (source).
After setting p9496 to 1 or 2, r9498 and r9499 are reset, r9497 is set to 0 and p9496 itself is set to 0.
p9495 BICO behavior to de-activated drive objects / Behav to deact obj
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, SERVO,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0
p9496 Restore BICO to the drive objects that are now activated / Rest BICO act obj
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, SERVO,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0