Siemens SINAMICS S Series - r0046.0...29 CO;BO: Missing enable sig; Missing enable sig

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-56
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
- the signal source in p0852 is a 0 signal.
Bit 08 = 1 (enable signal missing), if:
- the pulse enable via terminal EP is missing (booksize: X21, chassis: X41).
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enable if the fault is removed and was acknowledged and the
power-on inhibit withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- The commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 19 = 1 (internal pulse enable missing), if:
- synchronization is running between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling system ready signal via BI: p0266[1] missing.
Description: Displays missing enable signals that are preventing the closed-loop infeed control from being commissioned.
Dependency: Refer to: r0002
Note: The value r0046 = 0 indicates that all enable signals for the infeed are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a power-on inhibit.
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enable if the fault is removed and was acknowledged and the
power-on inhibit withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- The commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling system ready signal via BI: p0266[1] missing.
r0046.0...29 CO/BO: Missing enable sig / Missing enable sig
B_INF Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 8734
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No -
01 OFF2 enable missing Yes No -
08 EP terminals enable missing Yes No -
16 OFF1 enable internal missing Yes No -
17 OFF2 enable internal missing Yes No -
26 Infeed inactive or not operational Yes No -
29 Cooling system ready signal missing Yes No -