List of parameters
Parameters
1-143
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the maximum motor speed.
Dependency: Refer to: p1082
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
Description: Sets the maximum motor velocity.
Dependency: Refer to: p1082
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
Description: Set the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Notice: For VECTOR and SERVO, the following applies:
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is appropriately pre-
assigned. This is not the case when commissioning the motor (p0010 = 3).
Note: The parameter is automatically preset for motors from the motor list (p0301).
The parameter has no effect for induction motors.
For synchronous motors, a value must always be entered for the maximum motor current.
p0323 is a motor data. The user-selectable current limit is entered into p0640.
p0322[0...n] Maximum motor speed / Mot n_max
SERVO, VECTOR Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 0.0 [RPM]
p0322[0...n] Motor maximum velocity / Mot v_max
SERVO (Lin) Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [m/min] 1000.0 [m/min] 0.0 [m/min]
p0323[0...n] Maximum motor current / Mot I_max
SERVO Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 5722
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, FEM Expert list: 1
Min Max Factory setting
0.00 [Arms] 20000.00 [Arms] 0.00 [Arms]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S Series and is the answer not in the manual?

Siemens SINAMICS S Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals